E5
Bitzer
Critical

Oil Differential Pressure Failure

Delta P-MP10 detected low oil pressure for >90 seconds.

Possible causes

  • Low oil level
  • Clogged oil filter
  • Worn oil pump
  • Refrigerant in oil (foaming)

Recommended actions

  • Check oil level and color
  • Replace oil filter
  • Test pump operation
  • Perform pump-down to evacuate refrigerant from crankcase

Can't find your code? Talk to an expert