00079
Carrier Transicold
Warning

Check SV4 Circuit

Failure detected in the SV4 solenoid valve electrical circuit.

Possible causes

  • Defective SV4 coil (open or shorted)
  • Control relay failure
  • Loose connection point
  • Signal wire damage from controller

Recommended actions

  • Measure ohms on SV4 coil
  • Verify 12VDC at the connector
  • Check related fuses
  • Swap coil with a known good one if possible