00124
Carrier Transicold
Warning

Check Defrost Termination 1 Sensor

Defrost termination sensor 1 detects an out-of-range or open circuit condition.

Possible causes

  • Defective defrost sensor
  • Corroded or loose sensor connection
  • Wiring harness failure to the microprocessor

Recommended actions

  • Measure DTS1 sensor resistance
  • Clean contacts and tighten connectors
  • Replace sensor if reading does not match the temperature table