25300
Carrier Transicold
Critical

No Comm From Micro to STP3

Communication failure between the microprocessor and stepper motor module 3 (STP3).

Possible causes

  • Open or shorted CAN bus wiring
  • Loss of power supply to STP3
  • Internal board processor failure
  • Firmware incompatibility

Recommended actions

  • Check signal connectors in electrical panel
  • Measure power supply voltages
  • Verify CAN end-of-line resistance
  • Replace STP3 module