P14001
Carrier Transicold
Warning
C2 Chk Evap2 Superheat
Superheat out of range in evaporator 2 of compartment 2.
Possible causes
- EEV valve failure
- Obstruction in the liquid line
- Out of calibration evaporator sensors
Recommended actions
- Perform step test on the expansion valve
- Check pressure drop across filters
- Verify integrity of C2 sensors
- Replace detected defective components