150
Thermo King
Warning

Sensor Out of Range Low (DAS and HMI) (Zone)

A sensor (air, evaporator) is reporting a measurement below the minimum limit.

Possible causes

  • Short-circuited sensor
  • Defective signal input on the DAS module
  • Extreme environmental conditions out of range

Recommended actions

  • Verify the physical integrity of the affected sensor
  • Measure sensor resistance (compare with table)
  • Check connections on the expansion module