25
Thermo King
Warning

Alternator Check

System detects that the alternator is not charging the battery correctly.

Possible causes

  • Loose or broken alternator belt
  • Internal alternator voltage regulator failure
  • Loose excitation wire (no. 2) connection

Recommended actions

  • Measure alternator output voltage (should be >13.5V)
  • Adjust belt tension
  • Check connections at B+ terminal and ground