38
Thermo King
Warning
Electric Phase Reversed
The phases of the external power supply are reversed, which would cause inverse rotation.
Possible causes
- Incorrect connection at the wall outlet
- Miswired power cable
- Phase relay failure
- Changes in the site's electrical grid
Recommended actions
- Swap two phases at the power outlet
- Verify phase sequence with a phase meter
- Check the unit rotation sensor
- Inspect power cable integrity