45
Thermo King
Warning
Check Hot Gas or Hot Gas Bypass Circuit
Electrical failure detected in the hot gas bypass circuit.
Possible causes
- Burned hot gas solenoid coil
- Defective hot gas relay
- Open or shorted wiring
- Sulfated connectors
Recommended actions
- Measure bypass solenoid resistance
- Verify voltage at coil during heat cycle
- Test corresponding relay on the controller
- Clean electrical connections