513
Thermo King
Warning

Low Compressor Suction Ratio (Scroll Only)

Suction pressure ratio below safe operating limits for the Scroll compressor.

Possible causes

  • Low refrigerant charge
  • Restriction in suction line
  • ETV valve incorrectly closed
  • Defective suction pressure sensor

Recommended actions

  • Verify refrigerant levels and possible leaks
  • Check suction line filters
  • Verify ETV parameters in the controller
  • Inspect suction pressure sensor and wiring

Can't find your code? Talk to an expert