522
Thermo King
Warning
Battery Temperature Sensor Alarm
Battery temperature sensor reports out of range readings or is disconnected.
Possible causes
- Defective temperature sensor
- Broken or disconnected sensor wire
- Actual battery overheating from overcharging
- Corroded sensor connector
Recommended actions
- Verify physical connection of sensor on battery post
- Measure sensor resistance (NTC/PTC)
- Check if battery is physically hot
- Replace sensor if reading is erroneous