530
Thermo King
Warning

Low Pressure Differential (Scroll only)

Low differential pressure detected across the compressor (Scroll only).

Possible causes

  • Leaking internal compressor valves
  • Low refrigerant charge
  • Open hot gas bypass valve
  • Pressure sensor failure

Recommended actions

  • Check high and low pressures simultaneously
  • Check for bubbles in the liquid sight glass
  • Inspect gas bypass solenoids
  • Perform system thermal performance test